Closing a Missing Redundancy Path in a UPS Cooling System

Identifying a critical gap in the power redundancy strategy for a VRF-cooled UPS room.

Closing a Missing Redundancy Path in a UPS Cooling System

The Engineering Requirement

The VRF cooling system serving a UPS room was designed around two power sources, with one active source and one standby source. An automatic transfer switch (ATS) was therefore required to allow the system to transfer between the two sources when needed. During a site walkthrough, Beratung identified that the ATS had not been included in the bill of quantities and had not been installed.

Looking Beyond the Equipment

The site review also identified a related issue with the power routing between the outdoor and indoor units. The existing arrangement did not support the intended redundancy through the indoor units. Installing an ATS at the outdoor unit alone would therefore not have provided the required failover across the complete cooling system.

The Engineering Solution

Beratung addressed both elements together. The solution included:

The Outcome

Both changes were implemented before the project milestone. The intervention closed the identified redundancy gap and aligned the power routing with the intended failover strategy for the UPS room cooling system.